Chapter 15 – Inspecting Service Utility Equipment & Exterior Electrical
Chapter 15 – Inspecting Service Utility Equipment &
Exterior Electrical
We will continue our inspection with the service utility equipment and exterior electrical.
Have I mentioned that the most screwed up things I encountered during my inspection career were electrical issues created by residents? I truly am surprised that we do not hear more news stories about electrocuted homeowners. I think we should count our blessings.
The electric utility company will bring power into your main service panel from an underground line or overhead pole. The overhead power lines are strung from a pole and connected to a set of cables that run out of your main service panel.
Overhead power lines have maximum height and minimum clearance requirements when crossing over streets, driveways, walkways, roofs and within the physical reaching distance of windows, decks, stairs, porches, balconies and elevated walking surfaces. The following (unofficial) chart shows the minimum clearances accepted in most jurisdictions.
Wires over swimming pools are generally not allowed. Exceptions indicate lines should be at least 18 feet over the general area.
The power company service lines should not be in contact with trees and should be securely anchored to the building or the mast pipe. These cables should not rely on the connector splices to hold them in place.
The cables from the main service panel travel up through a pipe called a mast and out of a cap called a weatherhead.
The weatherhead is designed to face downward so water does not enter the pipe and flow into the service panel.
The mast pipe should not be bent and should be securely attached to the building. The cables themselves should have what is called a drip loop. The drip loop allows water to drip off the wire rather than run down into the mast and service panel.
The service panel exterior cover should be properly secured. Breakers should be labeled and any open spaces created by missing breakers should be sealed. Such open blanks are always listed as a HAZARD. This was another one of those over and over again findings.
The home inspector will be removing the main service panel’s interior cover, called the “Dead Cover”, and inspecting the inside of the box. It is called a “Dead Cover” for a reason.
HAZARD
DO NOT REMOVE THIS COVER UNLESS YOU ARE A LICENSED ELECTRICAL CONTRACTOR.
This is one of the areas you should not venture into. The risk of injury is very high for an inexperienced person. This also applies to any sub panels and old style fuse boxes located on the property.
Obstructions in front of the main service panel should be removed. Code requires clearance of at least 3 feet around the panel to allow access for a service technician or any person who needs to turn off the power in an emergency.
Conduit connections should be secure and watertight.
Exposed electrical wiring should be installed in conduit to protect it from the weather, animal and human contact.
Electrical wiring splices should be placed in a junction box. Splicing with electrical tape is not acceptable. Frayed wires and use of extension cords as permanent wiring should be removed if you want to avoid a note on a home inspection report.
Exterior outlets should be tested using the tester mentioned in a previous chapter. The chart in Chapter 7 indicates that exterior outlets should be G.F.C.I. protected from 1973 on.
Exterior outlets exposed to weather and moisture need to be protected with weather covers. Have a licensed electrical contractor replace these covers to avoid electrocution.
All exterior electrical fixtures (lighting, outlets, junction boxes, etc) must be properly secured and in good condition.
REPLACE ANY BURNED OUT LIGHT BULBS.
There, I said it again!
Hire a licensed electrical contractor for any electrical modifications or repairs. This includes any and all work done to the main service panel or any sub panels.
Your gas supply will either be natural gas provided by the utility company through a meter or propane delivered by truck to an onsite or community tank.
The natural gas meter and community propane gas meter should have a valve that can be turned off with a crescent wrench or pliers in the event of an emergency.
The shut off valve for a propane system will be at the tank and there may also be additional valves at the exterior of the building.
Be sure there is no odor of gas around any observable fitting, pipe or connection.
Be sure fuel oil tanks are properly vented and the filter is replaced per the supplier’s recommendations.
Backup generator systems that may be present for alternative electrical power in the event of blackouts must be installed with equipment that isolates the generator from the electrical grid when in use.
If you are running a generator and are still hooked into the grid, you are electrifying the power lines and could potentially injury a lineman who is working to restore the power to your neighborhood.
______________________________
UTILITY EQUIPMENT & EXTERIOR ELECTRICAL:
REMEDIES AND SOLUTIONS
Replace any broken or missing outlet, switch or junction box cover plates. They are inexpensive and easy to install. Please remember that the wires attached to the switches and receptacles inside junction boxes are potentially hot and dangerous.
The non-contact tester mentioned in a previous chapter can be used to
determine if there is power at a wire.
REPLACE ANY BURNED OUT BULBS.
There, I said it again.
If you smell gas contact the gas provider immediately. They will not charge you to identify the source of a leak and may even repair the problem at no charge.
Working with electricity can be hazardous and sometimes fatal. Do not attempt to work on electrical items or fixtures yourself. If you identify any electrical problems call a licensed electrical contractor.
Record your findings on the provided worksheets. Having identified and located these items before the electrical contractor arrives will expedite the time needed to correct them. In this game, time is money. You already know the advantage of having these issues resolved before the home inspector arrives.
PHOTO GALLERY
An additional 59 images with descriptive captions are available in the 27 Dollar Home Inspections eBook.
Click here to move on to
Chapter 16 – Inspecting Exterior Siding Materials & Exterior Walls
Chapter 16 – Inspecting Exterior Siding Materials & Exterior Walls
Tagged with: aerial power cable drip loop • antitrip pipe cover • cable should be secured • cables secured within how many feet of electrical panel • cables should be secure, usually by staples within ...of the electrical service panel. • Cables should be secured • cables should be secured (usually by staples) within_____of the electric service panel • cables should be secured by staples electrical service panal • cables should be secured by staples within feet of service panel • cables should be secured by staples within how many feet of the electrical service panel • cables should be secured by staples within how many feet of the service panel • cables should be secured how close to electrical panel • cables should be secured usally by staples within electrical panel • cables should be secured usually be staples within of the elctrical service panel • cables should be secured usually by staples wihtin how many feel of the electric service panel • cables should be secured usually by staples within • cables should be secured usually by staples within how many feel of the electrical service panel • cables should be secured usually by staples within of the electrical service panel • cables should be secured usually by staples within that of the electrical srvice panel? • cables should be secured usually, by staples within how many feet of the electrical panel • cables should be secured with cables within how many feet of the electrical service panel • cables should be secured with staples • cables should be secured with staples within • cables should be secured within electrical panek • cables should be secured within of electrical panel • cables should be secured within of service panel • cables should be secured within the electrical panel • Cables should be secured, usually by staples, within 1 feet of the electrical service panel. • cables should be secured, usually by staples, within how many feet of the electrical service panel • Cables should be secured, usually by staples, within _______ of the electrical service panel. • cables should be secured, usually by staples, within___of the electrical service panel • Cables should be securesd by staples witbinin how many feet of the service panel? • can an electric utility install a mast • can electrical wires run above a driveway for home inspection • can you cover electrical utility • clearance of oil tank to an electrical service panel • clearance of swimming pools to electric lines • deadcover for panel boxes • do you need an electrical inspection before utility will turn on power • does a homeowner have to fix defective items on a home inspection report in tennessee • does a propane generator need a drip loop • drip loop height • electical panel interior and exterior • electric company will not turn on power to house insecpion • electric main service panel and mast • electric mast pipe weather head • electric sevice exterior shut off • electric utility inspection checklist • ELECTRICAL PANEL DISTANCE FROM WINDOW • electrical panel proximity to windows • electrical problem in external house service • electrical service conduits should be secured to exterior of the hom • electrical utility equipment • electricity line connected to house exterior • exposed weatherhead leaked power • exterior electrical service and windows • Exterior electrical service housing • exterior electrical to main • exterior fuse boxes for pools • exterior housing for electrical equipment • exterior junction box height • exterior power line cover • exterior power panel • exterior service line • exterior service panel • exterior service panel code • exterior service panels should be secured • exterior utility box • exterior utility covers • exterior utility panels • frayed electric drip loop • height of drip loop • height of electrical service cables to home drip loop • height of overhead lines clearances over roofs • height requirement for overhead power lines running over driveways • HEIGHT REQUIREMENTS FOR OVERHEAD POWER FOR FUEL TANK • home electric line drip loop box cover • home inspections utility wires • how close can a service panel be to a window • how close should the cable be secured at the electrical service panel • how do I access an exterior main service panel • how is the electric pole secured to the house • how many feet around an electrical box • how many feet from electrical panel shoud cable be secured • how to cover exposed electrical wiring for home inspection • how to open an exterior electrical service panel • how to properly secure a weather-head to the house • indoor breaker panel clearance to window • inspecting the service cable on a house • main electric panel with exterior shut off • minimum clearance height for extior panels • minimum height for electric cable from pole to house over driveway • minimum height of electrical wire over driveway • minimum height of overhead electric cables crossing the street • minimum height of utility line above driveway • missing blanks in the electrical service pannle should be • missing blanks or breakers • missing blanks or breakers in an electrial panel should be • Missing blanks or breakers in an electrical service panal should be • missing blanks or breakers in the electrical • missing blanks or breakers in the electrical service panel • Missing blanks or breakers in the electrical service panel should be • missing blanks or breakers in the electrical services panel should be • missing blanks or breakers what should i do • no mast electric service cap • oregon minimum utility line height above driveway • outdoor exterior service panels mast • overhead power line clearance from windows • overhead power line inspection checklist • photo of a service weather head attached to pipe • photo of exterior electric service • PICs utility inspection checklist • pictures of exterior electric service panel installation • pole to the service panel mast • Power lines to Electrical service panel • Problem with looping at electric service box • remove exterior electrical main • residential exterior service panel height • secure electrical cable to house exterior • secure main electric service line • service panel clearance • service panel clearance from windows • service panel mast • service panel off during home inspection • should exterior main electrical shut off have an interior panel covering exposed wiring? • should there be a cover over the main electrical line • splicing utility power lines to main electric panel • swimming pool exterior fuse box equipment • usually by staples • UTILITIES EQUIPMENT & INSPECTION SERVICES • utility equipment inspection • utility mast wiring exterior • utility panels exterior • utility wires over swimming pool • weather cover home exterior electrical wires • what to cover main electrical line into house • where should hardwood to tile transition be in doorway • why are blanks in a breaker panel important • within 1 feet of the electrical service panel. • within ? of the electrical service panel
Filed under: Chapter 15 – Inspecting Service Utility Equipment & Exterior Electrical • Inspection Training
Like this post? Subscribe to my RSS feed and get loads more!